Specifications
Capacity: 3 kVA / 2700 W
Topology: high-frequency online double conversion, DSP control
Input voltage: 110–300 Vac (output derated at the low end)
Input frequency: 40–70 Hz, auto-sensing
Input power factor: ≥ 0.99 (active PFC)
Output voltage / 240 Vac, settable on the LCD
Voltage regulation: ±1%
Output power factor: 0.9
THDv: ≤ 2% linear load, ≤ 5% non-linear load
Crest factor: 3:1
Transfer time: 0 ms mains to battery, 4 ms inverter to bypass
Efficiency: 92% in mains mode, 87% in battery mode, 97% in ECO mode
Battery: 72 V DC, 6 × 12 V / 9 Ah sealed lead-acid, built in. The long-runtime (H) version has no internal batteries and runs from an external 72 V bank.
Charging: about 90% recharge in 3 h
Communications: RS232 standard; USB, RS485, SNMP and dry contacts optional
Noise: ≤ 5 ...